Description
Technical data | |
IECEx-certification of conformity | IECEx NEP 21.0020X, SEV 22 ATEX 0584X, IECEx SEV 22.0001X |
Ex Marking | Ex db eb mb IIC T5 Gb Ex tb IIIC T80˚C Db |
EC-Type Examination Certificate | SEV 22 ATEX 0584X |
Marking accd. to 2014/34/EU | EX II 2 G Ex eb mb IIC T6… T5 Gb EX II 2 D Ex tb IIIC T80°C Db |
Ambient temp | Normal: -40˚C to 55˚C for 3L, 5L, -40˚C to 50˚C for 7L |
Rated input volt | 100-240VAC 50/60Hz, DC 105-250V |
Power factor | >0.9 |
Colour Temperature | 5700K as standard, 3000K,4000K,5000K is available |
CRI | Cool white>70 as standard, CRI>80 is optional |
System watt* | VLL 3L series: <30W VLL 5L series: <55W VLL 7L series: <65W |
Lumen output | VLL 3L series: 3100Lm VLL 5L series: 6400Lm VLL 7L series: 7400Lm |
Material | GRP and PC |
Weight | VLL 3L series Normal and EM: 4.3Kg / 5.8Kg VLL 5L /7L series Normal and EM: 7.5Kg / 9.8Kg |
Terminals | Max 6mm² |
Entry Size | M20 as standard, M25 is available. |
Out line dimension (HxWxL) | VLL 3L series: 732x178x125 |
VLL 5L /7L series:1333x178x125 | |
Backup duration & Lumen percentage | Standard version EM1=1.5h,25% output. EM2=3h, 25% output is available. |
IP(IEC60598) | IP66 |
VLL LED Zone 1/21 GRP Linear Light Fixtures
The Crouse-Hinds series VLL LED linear fixture is specifically designed to replace fluorescent lighting in Zone 1 and 21 hazardous area applications. Manufactured with a high-strength glass-reinforced polyester enclosure and a polycarbonate cover, the VLL LED is engineered for long-life reliability and performance in areas prone to impact, corrosion, high vibration and adverse weather.
The VLL LED is available in 2-foot and 4-foot versions with three lumen-output options: 3100 lumens, 6400 lumens and 7400 lumens. High quality LEDs provide ~130 lumens per watt, reducing energy consumption and delivering cost savings.
The VLL LED is also is available with a self-contained battery system for emergency lighting applications.
Design features
EFFICIENCY
- Industry leading lumen efficacy up to ~130 lm/w reduces energy consumption and delivers cost savings
- Three lumen packages available from 3100 to 7400 lumens providing a versatile solution for different illumination applications
SAFETY AND RELIABILITY
- Rugged GRP design provides long-life relability in hazardous and harsh areas where corrosion, impact and adverse environments are common challenges
- IP66 rating, even under constant vibration
- Optional self-contained battery for emergency lighting applications delivers 25% of standard lumen output for 1.5-hours or 3-hours
EASY INSTALLATION AND MAINTENANCE
- Retrofit-friendly design includes optional sliding rail mounting system, which allows brackets to be easily adjusted to existing mounting holes
- Self-monitoring battery indicator provides easy visual of fixture status during routine maintenance checks
- Inhibit switch comes as standard on VLL LED emergency fixture, which is suitable for offshore unmanned platform applications
Standard materials
- Enclosure – fiberglass-reinforced polyester
- Protective cover – polycarbonate, frosted
- Gaskets – Silicone
- External hardware – stainless steel
Features & specifications
CEAG VLL LED Luminaires with high-quality LED chips, have extremely long lifespan. Multiple versions of the LED are available, providing ideal solutions for indoor or outdoor areas to retrofit existing fluorescent fixtures.
Model* | Nominal* lumens |
Wattage | Efficacy | Equivalent fluorescent |
VLL-3L | 3100 | <25W | >130~Lm/W | 2x18W |
VLL-5L | 6400 | <50W | >130~Lm/W | 2x36W |
VLL-7L | 7400 | <60W | >130~Lm/W | 2x58W |
- Lumen values apply to 5700K light colour, 70 CRI fixtures. Lumen output may vary slightly for different models.
- Tolerance+/-10%
- Optional emergency versions available (25% of standard lumen out put for 1.5-hours or 3-hours)
High efficacy up to 120 Lumens/W |
Low profile (3 in H) |
Four points of secondary retention |
2000 psi high pressure hose rated |
High vibration resistance |
0.23 A at 277 VAC, 0.63 A at 100 VAC |